“C” Group: Intelligent Terminal Functions
Configuring Drive
Parameters
3–52
C044 PID deviation level
setting
Sets the PID loop error
threshold |SP - PV|
(absolute value) to trigger
intelligent output [OD].
Range is 0.0 to 100%,
resolution is 0.1%
✘ ✔ 3.0 3.0 3.0 %
>C044 PID
LEVEL 003.0%
C061 Electronic thermal
warning level setting
Sets the threshold for intelli-
gent output [THM].
Range is 0 to 100%
✘ ✔ 80. 80. 80. %
>C061 E-THM
WARN 080%